Air-cooled Chiller KIC-5A
隐藏域元素占位
Category:
Keywords
- Product Description
- Specifications
-
- Commodity name: Air-cooled Chiller KIC-5A
- Commodity ID: KIC-5A
The “Kornai” series of industrial chillers can deliver chilled water at temperatures ranging from 3°C to 30°C, with special low-temperature models capable of producing water as cold as –25°C (with a temperature differential of no more than ±1°C). Air-cooled chillers are available with cooling capacities from 7,482 to 154,800 kcal/h (equivalent to compressor powers from 3 to 60 HP) and are widely used across various industries. For example, in the plastics industry—such as injection molding and vacuum forming—chillers can precisely control the temperature of plastic-molding molds, thereby shortening cycle times, accelerating product stabilization, preventing deformation and shrinkage, improving surface finish, and enhancing transparency. They are also suitable for cooling spindle lubricating oils and hydraulic fluids in CNC machine tools, coordinate boring machines, grinders, machining centers, modular machine tools, and other precision machine tools, enabling precise oil-temperature control, effectively reducing thermal deformation, and improving machining accuracy. In addition, these chillers are applicable to electroplating, food processing, dyeing, and other industries as well.
The “Kolnai” series of industrial chillers can deliver chilled water at temperatures ranging from 3°C to 30°C, with special low-temperature models capable of producing water as cold as –25°C (with a temperature differential of no more than ±1°C). Air-cooled chillers are available with cooling capacities from 7,482 to 154,800 kcal/h (equivalent to compressor powers from 3 to 60 HP) and are widely used across various industries. For example, in the plastics industry—particularly in injection molding and vacuum forming—chillers precisely control mold temperatures, thereby shortening cycle times, accelerating product solidification, preventing deformation and shrinkage, enhancing surface finish, and improving light transmission. They are also ideal for cooling spindle lubricating oils and hydraulic fluids in CNC machines, coordinate boring mills, grinders, machining centers, modular machine tools, and other precision machine tools, enabling precise oil-temperature control, effectively reducing thermal deformation, and improving machining accuracy. In addition, these chillers are suitable for use in electroplating, food processing, dyeing, and other industries as well.
Model Unit
UnitKIC-3A KIC-5A KIC-6A KIC-8A KIC-10A KIC-12A KIC-15A KIC-20A KIC-25A KIC-30A KIC-40A KIC-50A KIC-60A Cooling capacity
Refrigerating capacitykcal/h 7482 11782 14620 19264 23564 28724 36550 49536 57448 70692 94256 114896 154800 Keyword 8.7 13.7 17 22.4 27.4 33.4 42.5 57.6 66.8 82.2 109.6 133.6 180 Total Input Power kW
Total power inputKeyword 3.43 5.15 6.05 8.19 9.59/9.94 11.45/11.8 15.1 19.7/20.4 23.6 31.2 40.4 48.3 64.3 Refrigerant
Refrigerant- R22 Operation Control Mode
Running control method- Digital Microcomputer Temperature Controller Power supply
Power supply- 3N, 380V, 50Hz Safety Protection Device
Safety protection devices- Overload protection, reverse phase protection, high/low voltage protection, low water flow protection, low liquid level protection, freeze protection, and more. Compressor
CompressorForm Type Fully enclosed rotary or scroll type Compressor power in kW 2.7 4 4.9 6.6 8 9.6 12 16 19.2 24 32 38.4 54.4 Condenser
CondenserType High-efficiency red copper bushing with aluminum finned heat exchanger + low-noise external-rotor fan Air flow rate m³/h 3000 5000 6000 8000 10000 12000 15000 20000 25000 30000 40000 50000 60000 Fan power kW 0.18 × 2 0.2 × 2 0.2 × 2 0.42 × 2 0.42 × 2 0.55 × 2 0.8 × 2 1.1 times 2 1.1 times 2 0.8 × 4 1.1×4 1.1×4 1.1×4 Evaporator
EvaporatorType Water-tank coil type/dry shell-and-tube type Inlet and outlet pipe diameter (inches) 1 1 1 1.5 1.5 2 2 2.5 2.5 2.5 3 3 3 Water tank capacity L
Water tank capacityL 50 50 70 120 120 120 120 200 200 200 400 400 400 Pump
PumpFlow rate L/min 40 50 50 80 80/100 80/100 150 150/200 200 300 300 500 500 Pressure bar 1.7 1.7 1.7 1.7 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1 2.1 Power kW 0.37 0.75 0.75 0.75 0.75/1.1 0.75/1.1 1.5 1.5/2.2 2.2 4 4 5.5 5.5 External dimensions
External dimensionsLength A mm 1122 1122 1322 1530 1530 1530 2000 2000 2000 2300 2300 2300 2800 Width B mm 620 620 734 800 800 800 1000 1000 1000 1800 1800 1800 1800 High C mm 1180 1180 1300 1480 1480 1480 1960 1960 1960 1800 1800 1800 1800 Refrigerant Charge (kg)
Refrigerant fillingkilogram 2.7 4.3 5 7 8.6 10 13 17 21 25 33 42 50 Remarks 1. The cooling capacity is based on a chilled water inlet temperature of 15°C, a chilled water outlet temperature of 10°C, and an ambient temperature of 35°C.
2. The Company reserves the right to modify the above parameters without prior notice. Custom specifications may be designed and modified upon request.
Previous Page
Next Page
Product Details
The “Kolnai” series of industrial chillers can deliver chilled water at temperatures ranging from 3°C to 30°C, with special low-temperature models capable of producing water as cold as –25°C (with a temperature differential of no more than ±1°C). Air-cooled chillers are available with cooling capacities from 7,482 to 154,800 kcal/h (equivalent to compressor powers from 3 to 60 HP) and are widely used across various industries. For example, in the plastics industry—particularly in injection molding and vacuum forming—chillers precisely control mold temperatures, thereby shortening cycle times, accelerating product solidification, preventing deformation and shrinkage, enhancing surface finish, and improving light transmission. They are also ideal for cooling spindle lubricating oils and hydraulic fluids in CNC machines, coordinate boring mills, grinders, machining centers, modular machine tools, and other precision machine tools, enabling precise oil-temperature control, effectively reducing thermal deformation, and improving machining accuracy. In addition, these chillers are suitable for use in electroplating, food processing, dyeing, and other industries as well.
| Model | Unit Unit |
KIC-3A | KIC-5A | KIC-6A | KIC-8A | KIC-10A | KIC-12A | KIC-15A | KIC-20A | KIC-25A | KIC-30A | KIC-40A | KIC-50A | KIC-60A |
| Cooling capacity Refrigerating capacity |
kcal/h | 7482 | 11782 | 14620 | 19264 | 23564 | 28724 | 36550 | 49536 | 57448 | 70692 | 94256 | 114896 | 154800 |
| Keyword | 8.7 | 13.7 | 17 | 22.4 | 27.4 | 33.4 | 42.5 | 57.6 | 66.8 | 82.2 | 109.6 | 133.6 | 180 | |
| Total Input Power kW Total power input |
Keyword | 3.43 | 5.15 | 6.05 | 8.19 | 9.59/9.94 | 11.45/11.8 | 15.1 | 19.7/20.4 | 23.6 | 31.2 | 40.4 | 48.3 | 64.3 |
| Refrigerant Refrigerant |
- | R22 | ||||||||||||
| Operation Control Mode Running control method |
- | Digital Microcomputer Temperature Controller | ||||||||||||
| Power supply Power supply |
- | 3N, 380V, 50Hz | ||||||||||||
| Safety Protection Device Safety protection devices |
- | Overload protection, reverse phase protection, high/low voltage protection, low water flow protection, low liquid level protection, freeze protection, and more. | ||||||||||||
| Compressor Compressor |
Form Type | Fully enclosed rotary or scroll type | ||||||||||||
| Compressor power in kW | 2.7 | 4 | 4.9 | 6.6 | 8 | 9.6 | 12 | 16 | 19.2 | 24 | 32 | 38.4 | 54.4 | |
| Condenser Condenser |
Type | High-efficiency red copper bushing with aluminum finned heat exchanger + low-noise external-rotor fan | ||||||||||||
| Air flow rate m³/h | 3000 | 5000 | 6000 | 8000 | 10000 | 12000 | 15000 | 20000 | 25000 | 30000 | 40000 | 50000 | 60000 | |
| Fan power kW | 0.18 × 2 | 0.2 × 2 | 0.2 × 2 | 0.42 × 2 | 0.42 × 2 | 0.55 × 2 | 0.8 × 2 | 1.1 times 2 | 1.1 times 2 | 0.8 × 4 | 1.1×4 | 1.1×4 | 1.1×4 | |
| Evaporator Evaporator |
Type | Water-tank coil type/dry shell-and-tube type | ||||||||||||
| Inlet and outlet pipe diameter (inches) | 1 | 1 | 1 | 1.5 | 1.5 | 2 | 2 | 2.5 | 2.5 | 2.5 | 3 | 3 | 3 | |
| Water tank capacity L Water tank capacity |
L | 50 | 50 | 70 | 120 | 120 | 120 | 120 | 200 | 200 | 200 | 400 | 400 | 400 |
| Pump Pump |
Flow rate L/min | 40 | 50 | 50 | 80 | 80/100 | 80/100 | 150 | 150/200 | 200 | 300 | 300 | 500 | 500 |
| Pressure bar | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.9 | 2.1 | 2.1 | 2.1 | 2.1 | 2.1 | 2.1 | |
| Power kW | 0.37 | 0.75 | 0.75 | 0.75 | 0.75/1.1 | 0.75/1.1 | 1.5 | 1.5/2.2 | 2.2 | 4 | 4 | 5.5 | 5.5 | |
| External dimensions External dimensions |
Length A mm | 1122 | 1122 | 1322 | 1530 | 1530 | 1530 | 2000 | 2000 | 2000 | 2300 | 2300 | 2300 | 2800 |
| Width B mm | 620 | 620 | 734 | 800 | 800 | 800 | 1000 | 1000 | 1000 | 1800 | 1800 | 1800 | 1800 | |
| High C mm | 1180 | 1180 | 1300 | 1480 | 1480 | 1480 | 1960 | 1960 | 1960 | 1800 | 1800 | 1800 | 1800 | |
| Refrigerant Charge (kg) Refrigerant filling |
kilogram | 2.7 | 4.3 | 5 | 7 | 8.6 | 10 | 13 | 17 | 21 | 25 | 33 | 42 | 50 |
| Remarks | 1. The cooling capacity is based on a chilled water inlet temperature of 15°C, a chilled water outlet temperature of 10°C, and an ambient temperature of 35°C. 2. The Company reserves the right to modify the above parameters without prior notice. Custom specifications may be designed and modified upon request. |
|||||||||||||
- Strong safety performance: Provide multiple anti-theft designs to ensure the safety of home and property.
- High durability: Made of high-quality materials, corrosion-resistant and wear-resistant, with a long service life.
- Appearance diversity: Rich design styles, perfect match with various decorations.
- Easy operation: Intelligent design, no key required, simple and efficient to use.
- Multifunctionality: With alarm prompts and networking functions, it meets the needs of multiple scenarios.
- Easy installation: Compatible with a variety of door types, quick installation, and strong adaptability.
Certificate
FAQ
Q
What are the common reasons for the mold temperature controller alarming and shutting down?
A
Common reasons include high-temperature protection, low liquid level alarm, overload protection, heating element failure, or pump malfunction.
Q
Why is the cooling performance of the chiller poor?
A
Possible causes include insufficient refrigerant, blocked condenser, compressor failure, or pipeline leakage. Inspections and repairs are needed.
Q
What is the working principle of a mold temperature controller (MTC)?
A
The MTC heats or cools the medium (such as water or thermal oil) to a set temperature and then circulates it through the mold or equipment via a pump to achieve precise temperature control.
Q
Why is the mold temperature controller heating up slowly?
A
Possible reasons include insufficient heating power, pump failure, pipeline blockage, or insufficient medium. These should be checked and resolved step by step.
Q
What is the difference between a mold temperature controller and a chiller?
A
The MTC is used for heating and maintaining the temperature of equipment or molds, while the chiller is mainly used for quickly cooling equipment or molds to lower the temperature.
Contact
Fax: 86-750-3609612
Add: No. 38, Yecheng Industrial Zone, Kautou Star Village, Jianghai District, Jiangmen, Guangdong, China