Water-Cooled Chiller KIC-30W
隐藏域元素占位
Category:
Keywords
- Product Description
- Specifications
-
- Commodity name: Water-Cooled Chiller KIC-30W
- Commodity ID: KIC-30W
The “Kolnai” series of industrial chillers can deliver chilled water at temperatures ranging from 3°C to 30°C, with special low-temperature models capable of producing ice water as cold as –25°C (with a temperature differential of no more than ±1°C). Water-cooled chillers offer cooling capacities from 8,514 to 163,400 kcal/h (equivalent to compressor powers from 3 to 60 HP) and are widely used across various industries. For example, in the plastics industry—particularly in injection molding and vacuum forming—chillers precisely control mold temperatures, thereby shortening cycle times, accelerating product stabilization, preventing deformation and shrinkage, enhancing surface finish, and improving light transmission. They are also ideal for cooling spindle lubricating oils and hydraulic fluids in CNC machines, coordinate boring mills, grinders, machining centers, modular machine tools, and other precision machine tools, enabling precise oil-temperature control, effectively reducing thermal deformation, and improving machining accuracy. In addition, these chillers are suitable for use in electroplating, food processing, dyeing and bleaching, and other industries as well.
The “Kolnai” series of industrial chillers can deliver chilled water at temperatures ranging from 3°C to 30°C, with special low-temperature models capable of producing ice water as cold as –25°C (with a temperature differential of no more than ±1°C). These water-cooled chillers offer cooling capacities from 8,514 to 163,400 kcal/h (equivalent to compressor powers from 3 to 60 HP) and are widely applicable across various industries. For instance, in the plastics industry—such as injection molding and vacuum forming—chillers precisely control the temperature of plastic-molding molds, thereby shortening cycle times, accelerating product stabilization, preventing deformation and shrinkage, enhancing surface finish, and improving light transmission. They are also ideal for cooling spindle lubricating oils and hydraulic fluids in CNC machine tools, coordinate boring machines, grinders, machining centers, modular machine tools, and other precision machine tools, enabling precise oil-temperature control, effectively reducing thermal deformation, and improving machining accuracy. In addition, these chillers are suitable for use in electroplating, food processing, dyeing and bleaching, and other industries as well.
Model
Unit
KIC-3W KIC-5W KIC-6W KIC-8W KIC-10W KIC-12W KIC-15W KIC-20W KIC-25W KIC-30W KIC-40W KIC-50W KIC-60W Cooling capacity
kcal/h 8514 13158 17028 21844 26316 32078 41108 55900 64156 83850 111800 128312 163400 Total Input Power
Keyword 9.9 15.3 19.8 25.4 30.6 37.3 47.8 65 74.6 97.5 130 149.2 190 Total Input Power
Keyword 2.5 4.04 4.57 6.03 7.33/7.68 8.16/8.51 11.32 14.56/15.26 17.02 23.59 30.12 35.14 45.5 Refrigerant
R22 Operation Control Mode
Digital Microcomputer Temperature Controller Power supply
3N, 380V, 50Hz Safety Protection Device
Overload protection, reverse phase protection, high/low voltage protection, low water flow protection, low liquid level protection, freeze protection, and more.
Compressor
Form
Fully enclosed rotary or scroll type Compressor power
Keyword 2.13 3.29 3.82 5.28 6.58 7.41 9.82 13.06 14.82 19.59 26.12 29.64 40 Condenser
Type
Shell-and-tube type (standard water-side pressure rating: 0.6 MPa to 0.8 MPa)
Water flow rate
cubic meters per hour 2.13 3.29 4.26 5.46 8.02 8.02 10.28 13.98 16.04 20.96 27.95 32.08 40.85 Plumbing connection
Inch 1 1 1 1.5 1.5 2 2 2 2.5 2.5 3 3 3 Evaporator
Type
Water-tank coil type / Dry shell-and-tube type Inlet and outlet pipe diameter
Inch 1 1 1 1.5 2 2 2 2.5 2.5 2.5 3 3 3 Water tank capacity
L 50 50 70 120 120 120 120 200 200 200 400 400 400 Pump
Traffic
L/min 40 50 50 80 80/100 80/100 150 150/200 200 300 300 500 500 Pressure
bar 1.7 1.7 1.7 1.7 1.7 1.7 1.9 2.1 2.1 2.1 2.1 2.1 2.1 Power
Keyword 0.37 0.75 0.75 0.75 0.75/1.1 0.75/1.1 1.5 1.5/2.2 2.2 4 4 5.5 5.5 External dimensions
A (long)
mm 935 935 935 1320 1320 1320 1770 1770 1770 2000 2400 2400 2400 B (width)
mm 900 900 900 650 650 650 735 735 735 1000 1000 1000 1000 C (high)
mm 500 900 900 1370 1370 1370 1610 1610 1610 1850 1800 1800 1800 Refrigerant charge
kilogram 1.7 2.8 4.5 4.4 5.6 6.8 8.4 11.2 13.6 16.8 22.4 27.2 34 Note 1: The cooling capacity is based on a chilled water inlet temperature of 15°C, an outlet temperature of 10°C, and an ambient temperature of 35°C.
2. The Company reserves the right to modify the above parameters without prior notice. Custom specifications may be designed and modified upon request.
Previous Page
Next Page
Product Details
The “Kolnai” series of industrial chillers can deliver chilled water at temperatures ranging from 3°C to 30°C, with special low-temperature models capable of producing ice water as cold as –25°C (with a temperature differential of no more than ±1°C). These water-cooled chillers offer cooling capacities from 8,514 to 163,400 kcal/h (equivalent to compressor powers from 3 to 60 HP) and are widely applicable across various industries. For instance, in the plastics industry—such as injection molding and vacuum forming—chillers precisely control the temperature of plastic-molding molds, thereby shortening cycle times, accelerating product stabilization, preventing deformation and shrinkage, enhancing surface finish, and improving light transmission. They are also ideal for cooling spindle lubricating oils and hydraulic fluids in CNC machine tools, coordinate boring machines, grinders, machining centers, modular machine tools, and other precision machine tools, enabling precise oil-temperature control, effectively reducing thermal deformation, and improving machining accuracy. In addition, these chillers are suitable for use in electroplating, food processing, dyeing and bleaching, and other industries as well.
| Model |
Unit |
KIC-3W | KIC-5W | KIC-6W | KIC-8W | KIC-10W | KIC-12W | KIC-15W | KIC-20W | KIC-25W | KIC-30W | KIC-40W | KIC-50W | KIC-60W | |
| Cooling capacity |
kcal/h | 8514 | 13158 | 17028 | 21844 | 26316 | 32078 | 41108 | 55900 | 64156 | 83850 | 111800 | 128312 | 163400 | |
| Total Input Power |
Keyword | 9.9 | 15.3 | 19.8 | 25.4 | 30.6 | 37.3 | 47.8 | 65 | 74.6 | 97.5 | 130 | 149.2 | 190 | |
| Total Input Power |
Keyword | 2.5 | 4.04 | 4.57 | 6.03 | 7.33/7.68 | 8.16/8.51 | 11.32 | 14.56/15.26 | 17.02 | 23.59 | 30.12 | 35.14 | 45.5 | |
| Refrigerant |
R22 | ||||||||||||||
| Operation Control Mode |
Digital Microcomputer Temperature Controller | ||||||||||||||
| Power supply |
3N, 380V, 50Hz | ||||||||||||||
| Safety Protection Device |
Overload protection, reverse phase protection, high/low voltage protection, low water flow protection, low liquid level protection, freeze protection, and more. |
||||||||||||||
| Compressor |
Form |
Fully enclosed rotary or scroll type | |||||||||||||
| Compressor power |
Keyword | 2.13 | 3.29 | 3.82 | 5.28 | 6.58 | 7.41 | 9.82 | 13.06 | 14.82 | 19.59 | 26.12 | 29.64 | 40 | |
| Condenser |
Type |
Shell-and-tube type (standard water-side pressure rating: 0.6 MPa to 0.8 MPa) |
|||||||||||||
| Water flow rate |
cubic meters per hour | 2.13 | 3.29 | 4.26 | 5.46 | 8.02 | 8.02 | 10.28 | 13.98 | 16.04 | 20.96 | 27.95 | 32.08 | 40.85 | |
| Plumbing connection |
Inch | 1 | 1 | 1 | 1.5 | 1.5 | 2 | 2 | 2 | 2.5 | 2.5 | 3 | 3 | 3 | |
| Evaporator |
Type |
Water-tank coil type / Dry shell-and-tube type | |||||||||||||
| Inlet and outlet pipe diameter |
Inch | 1 | 1 | 1 | 1.5 | 2 | 2 | 2 | 2.5 | 2.5 | 2.5 | 3 | 3 | 3 | |
| Water tank capacity |
L | 50 | 50 | 70 | 120 | 120 | 120 | 120 | 200 | 200 | 200 | 400 | 400 | 400 | |
| Pump |
Traffic |
L/min | 40 | 50 | 50 | 80 | 80/100 | 80/100 | 150 | 150/200 | 200 | 300 | 300 | 500 | 500 |
| Pressure |
bar | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.9 | 2.1 | 2.1 | 2.1 | 2.1 | 2.1 | 2.1 | |
| Power |
Keyword | 0.37 | 0.75 | 0.75 | 0.75 | 0.75/1.1 | 0.75/1.1 | 1.5 | 1.5/2.2 | 2.2 | 4 | 4 | 5.5 | 5.5 | |
| External dimensions |
A (long) |
mm | 935 | 935 | 935 | 1320 | 1320 | 1320 | 1770 | 1770 | 1770 | 2000 | 2400 | 2400 | 2400 |
| B (width) |
mm | 900 | 900 | 900 | 650 | 650 | 650 | 735 | 735 | 735 | 1000 | 1000 | 1000 | 1000 | |
| C (high) |
mm | 500 | 900 | 900 | 1370 | 1370 | 1370 | 1610 | 1610 | 1610 | 1850 | 1800 | 1800 | 1800 | |
| Refrigerant charge |
kilogram | 1.7 | 2.8 | 4.5 | 4.4 | 5.6 | 6.8 | 8.4 | 11.2 | 13.6 | 16.8 | 22.4 | 27.2 | 34 | |
| Note 1: The cooling capacity is based on a chilled water inlet temperature of 15°C, an outlet temperature of 10°C, and an ambient temperature of 35°C. 2. The Company reserves the right to modify the above parameters without prior notice. Custom specifications may be designed and modified upon request. |
|||||||||||||||
- Strong safety performance: Provide multiple anti-theft designs to ensure the safety of home and property.
- High durability: Made of high-quality materials, corrosion-resistant and wear-resistant, with a long service life.
- Appearance diversity: Rich design styles, perfect match with various decorations.
- Easy operation: Intelligent design, no key required, simple and efficient to use.
- Multifunctionality: With alarm prompts and networking functions, it meets the needs of multiple scenarios.
- Easy installation: Compatible with a variety of door types, quick installation, and strong adaptability.
Certificate
FAQ
Q
Why does the oil temperature machine catch fire?
A
The fire situation of the oil temperature machine can be divided into two types: 1. The heat transfer oil itself is not touched by other items and spontaneous combustion occurs. Reason: A. The temperature of the heat transfer oil reaches the ignition point and catches fire in contact with air. B. The temperature of the heat transfer oil reaches the flash point and the volatile gas in the oil tank reaches a certain concentration.
Q
In industrial applications, air-cooled chiller refrigeration compressor protection devices have what role?
A
In industrial applications, chilled water or other liquid cooling is pumped through process or laboratory equipment. Chillers are used to control the cooling of products, mechanisms and plant machinery in all walks of life. They are commonly used in the plastics industry for injection and blow molding, metal processing and cutting.
Q
What are the application fields and functions of ultra-high temperature mold temperature machine
A
Ultra-high temperature mold temperature machine is a type of equipment classified according to the temperature control range of the mold temperature machine, corresponding to ordinary mold temperature machine and high temperature mold temperature machine, etc. Due to the different circulating heating media used, it is divided into two types: oil circulating mold temperature machine and water circulating mold temperature machine.
Q
How to extend the service life of high temperature oil mold temperature machine?
A
The application of mold temperature machine in various industries is very common. The equipment uses water or heat transfer oil as heat transfer medium. Through PID self-tuning adjustment method, the temperature of the application equipment can be accurately controlled.
Q
Why does the cold water machine have high pressure failure
A
Several common faults of cold water machine compressor briefly summarizes the common cold water machine fault problems, which can be roughly divided into four categories: 1. compressor fault: 1. first check whether the compressor can start normally, and measure whether the compressor voltage is normal.
Contact
Fax: 86-750-3609612
Add: No. 38, Yecheng Industrial Zone, Kautou Star Village, Jianghai District, Jiangmen, Guangdong, China